undefined
+
  • undefined

6kV-35kV Medium-Voltage Cross-Linked Polyethylene Insulated Power Cables

Service hotline:

Product Description: Rated voltage (6–35) kV cross-linked polyethylene-insulated power cables are suitable for use in power systems up to 35 kV, making them ideal for both transmission and distribution systems as carriers of electrical power.

 

Implementation standard: GB/T 12706.2-2020 GB/T 12706.3-2020

 

Usage characteristics:

Rated voltages U0/U are 3.6/6, 6/6, 6/10, 8.7/10, 8.7/15, 12/20, 18/30, 21/35, and 26/35 kV;

The long-term permissible operating temperature of the cable conductor is 90°C.

Minimum bending radius of the cable:

Project

Single-core cable

Three-core cable

Non-armored

Armored

Non-armored

Armored

Minimum cable bending radius during installation

20D

15D

15D

12D

Minimum bending radius near the junction box and terminals (but ensure careful control of bending, e.g., by using a shaped guide plate).

15D

12D

12D

10D

Note: D is the cable outer diameter

 

Common models

Name

Uses

Copper core

Aluminum core

YJV

YJLV

Cross-linked polyethylene-insulated polyvinyl chloride-sheathed power cable

Indoors, tunnels, pipelines, cable trenches, and more

YJY

YJLY

Cross-linked polyethylene insulated polyethylene sheathed power cable

YJV22
(YJV62)

YJLV22
(YJLV62)

Cross-linked polyethylene insulated steel tape armored PVC sheathed power cable

Indoors, tunnels, pipelines, cable trenches
Buried directly underground, capable of withstanding mechanical pressure

YJV23
(YJV63)

YJLV23
(YJLV63)

Cross-linked polyethylene insulated steel tape armored polyethylene sheathed power cable

YJV32

YJLV32

Cross-linked polyethylene-insulated, fine steel wire-armored, PVC-sheathed power cable

Suitable for stepped or vertical installations, capable of withstanding mechanical tension.

YJV33

YJLV33

Cross-linked polyethylene insulated, fine steel wire-armored, polyethylene-sheathed power cable

 

01